LiYY-DIN Dca
Power, control and signalling
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI LIYY <formation> IEC 60332-3-24 <lot> <year> DCA-S3,D0,A3
Manufacturing characteristics
Core
Flexible bare copper conductor, class 5
Insulation
PVC flame retardant compound
Stranding
Cores twisted/stranded in concentric layers
Outer sheath
PVC flame retardant compound
Colours
Cores identifcation:
DIN 47100
Outer sheath colour:
Grey (based on RAL 7001)
Electrical characteristics
Tensione di esercizio anime
300/500V
Tensione di esercizio guaina esterna
300/500V
Tensione di prova
2000V
Certifications
Standard
IEC 60228
IEC 60332-3-24 Cat.C
Reaction to Fire Class
EN 50575:2016 Dca - s3, d0, a3
Temperature
Temperatura minima di esercizio
• Fixed laying -25°C • Occasional mobile laying w/o stress -5°C
Temperatura massima di esercizio
• Fixed laying +70°C • Occasional mobile laying w/o stress +70°C
Temperatura massima cortocircuito
+160°C
On request
• Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In duct or cable tray
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Multi-core cable for control, signaling, command and measurement systems with scaled-down outer dimension and excellent flexibility.
Commonly used in intercom systems, electronic control equipment, office machines, measuring devices, and in general wherever a small diameter cable is required. It has excellent flexibility and is lightweight.
Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
Underground laying is not permitted even if protected.