Solar energy - Low smoke zero halogen

Marcatura 
Marcatura: CE 2479 SPECIALCAVI BALDASSARI H1Z2Z2-K <formazione> IEMMEQU HAR <lotto> <anno> DCA-S2,D2,A1
Manufacturing characteristics
Core 

Flexible tinned copper, class 4

Insulation 

LSZH cross-linked elastometric compound

Outer sheath 

Special LSZH cross-linked elastometric compound, UV resistant

Colours 

Cores identification:
White
Outer sheath colour:
Black or Red (based on RAL 9005 or 3000)

Electrical characteristics
Tensione di esercizio anime 

Nominal operating voltage: 1.0kV C.A. - 1.5kV C.C. (also to earth)
Maximum operating voltage: 1.2kV C.A. - 1.8kV C.C. (also to earth)

Tensione di esercizio guaina esterna 
Nominal operating voltage: 1.0kV C.A. - 1.5kV C.C. (also to earth) Maximum operating voltage: 1.2kV C.A. - 1.8kV C.C. (also to earth)
Tensione di prova 

15 kV C.C.

Certifications
Standard 

EN 50618
EN 60228 EN 50395
EN 50618
EN 50618 EN 50395 EN 62230
EN 50618 EN 50396 EN 60228
EN 60811-401 EN 50618
EN 60811-504 EN 60811-505 EN 60811-506 EN 50618
EN 60811-403 EN 50396 EN 50618
EN 50618 EN 50289-4-17 metodo A
EN 50618
EN 60068-2-78
EN 60811-503
EN 60332-1-2
EN 61034-2 (LT≥60%)
EN 50525-1
EN 50618 EN 60216-1 EN 60216-2

Reaction to Fire Class 
EN 50575:2016 Dca - s2, d2, a1
Temperature
Temperatura minima di esercizio 

-40°C

Temperatura massima di esercizio 

+90°C

Temperatura massima cortocircuito 
+250°C
On request 
  • Galvanized steel braid armour, reaction to fire class Eca
  • ​Aluminium conductor, reaction to fire class Eca
Laying conditions
Temperatura minima di posa -25°C
Raggio minimo di posa d4
Max tensile stress: see tecnica data sheet
Fixed Laying
In open air
In duct or cable tray
In buried trough
Buried with protection
In buried duct
Directly buried
Applications 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Single-core halogen free cable suitable for interconnecting various components in solar and photovoltaic systems. H1Z2Z2-K cable has an excellent resistance to UV rays and weather conditions.
The cable is estimated to operate about 25 years (EN 50618). The period expected for its use at 120°C maximum core temperature and at 90°C maximum ambient temperature is limited to 20.000 hours.
Suitable for fixed laying outdoors and inside buildings, without protection or inside visible or embedded pipes.
Suitable for applications not covered by CPR Regulations and for installations in a closed environment, excluding cases with specific initiation/propagation fire hazards where is recommended the use of cables with higher fire response performance (at least Cca-s3,d1,a3).
Direct or indirect underground and outside laying is permitted. Presence of water: condition AD8 (adapted to EN 50525-2-21).

H1Z2Z2-K Dca | Specialcavi Baldassari