Data transmission and instrumentation

ULCX FRXHOHR16 Cca
Marcatura 
<meters> CE 0987 SPECIALCAVI BALDASSARI ULCX FRXHOHR <formation> 450/750V CEI 20-22 II <lot> <year> DCA-S3,D0,A3
Manufacturing characteristics
Core 

Flexible tinned copper

Insulation 

PVC compound, R2 type

Stranding 

Cores twisted in pairs

Pairs stranded in concentric layers

Wrapping and protection 

1° wrapping and protection: 

Polyester tape on single pair

2° wrapping and protection: 

Overall polyester tape

Screen 

1° shield:

Aluminium/polyester tape on single pair with flexible tinned copper drain-wire

2° shield:

Overall aluminium/polyester tape with flexible tinned copper drain-wire

Outer sheath 

PVC compound, R16 type

Colours 

Cores identification:

DIN 47100

Outer sheath colour:

Grey (based on RAL 7035)

Electrical characteristics
Tensione di esercizio anime 

300/300V

Tensione di esercizio guaina esterna 
450/750V
Tensione di prova 

1500V

Certifications
Standard 

CEI 20-29 IEC 60228
CEI 20-11
CEI 20-22 II
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI UNEL 36762

Reaction to Fire Class 
EN 50575:2016 Dca - s3, d0, a3
Temperature
Temperatura minima di esercizio 

-15°C

Temperatura massima di esercizio 

+70°C

Temperatura massima cortocircuito 
+160°C
On request 

• Galvanized steel braid armour with 450/750V insula-tion voltage outer sheath

• Outer sheath with 0.6/1kV voltage for laying outdoors or in buried cable trays

• Customized cores identification/outer sheath colours

Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d10
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In open air (0.6/1kV)
In duct or cable tray
Applications 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.

Multipair cable shielded on the single pair and overall, suitable for electronic, data transmission between central and peripheral units through ports (RS232) and for interconnections between devices where a high quality of the transmitted signals is required.

This cable can always be installed in coexistence with 450/750V power cables. Furthermore, if it’s used to supply power to category 0 systems (nominal voltage less than or equal to 50V AC, or 120V non-inverted DC), it can also be installed in coexistence with 0.6/1kV power cables that supply 230/400V nominal voltage loads.

Underground laying is not permitted, even if protected.

ULCX FRXHOHR16 Cca | Specialcavi Baldassari

Error

The website encountered an unexpected error. Please try again later.