Data transmission and instrumentation

LiYCY-TP FR2XOH2R16 Cca
Marcatura 
<metrica progressiva> CE 0987 SPECIALCAVI BALDASSARI LIYCY-TP <formazione> 450/750V CEI 20-22 II <lotto> <anno> CCA-S2,D0,A3
Manufacturing characteristics
Core 

Flexible bare copper, class 5

Insulation 

PVC compound, flame retardant

Stranding 

Cores twisted in pairs

Pairs stranded in concentric layers 

Wrapping and protection 

Overall polyester tape

Screen 

Overall tinned copper braid 

Outer sheath 

PVC compound, flame retardant

Colours 

Cores identification:

DIN 47100

Outer sheath colour:

Grey (based on RAL 7001)

Electrical characteristics
Tensione di esercizio anime 
  • 300/500V section ≤ 0.75 mm²
  • 450/750V section ≥ 1.00 mm²
Tensione di esercizio guaina esterna 
450/750V
Tensione di prova 
  • 2000V section ≤ 0.75 mm²
  • 2500V section ≥ 1.00 mm²
Certifications
Standard 

CEI 20-29 IEC 60228
CEI 20-11
CEI 20-22 II CEI EN 60332-3-24 Cat.C  IEC 60332-3-24 Cat.C
CEI UNEL 36762

Reaction to Fire Class 
EN 50575:2016 Cca - s2, d0, a3
Temperature
Temperatura minima di esercizio 
  • Fixed laying: -25°C
  • Occasional mobile laying w/o stress: -5°C
Temperatura massima di esercizio 
  • Fixed laying: +70°C
  • Occasional mobile laying w/o stress: +70°C
Temperatura massima cortocircuito 
+160°C
On request 
  • Customized cores identification/outer sheath colours
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d10
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
Applications 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.

Multi-pair cable with overall shield for data transmission in electronics and computers, for signalling, measurement, command and control systems, and generally where there is a need for efficient protection from external electromagnetic interferences and compact sizes. 

Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.

Underground laying is not permitted even if protected.