Power, control and signalling - Low smoke zero halogen

HSLH-OB/-JB/-OZ/-JZ Cca
Marcatura 
<meters> CE 0987 SPECIALCAVI BALDASSARI HSLH <formation> IEC 60332-3-24 <lot> <year> CCA-S1A,D0,A1
Manufacturing characteristics
Core 

Flexible bare copper conductor, class 5

Insulation 

LSZH thermoplastic compound

Stranding 

Cores twisted/stranded in concentric layers

Outer sheath 

LSZH thermoplastic compound

Colours 

Cores identifcation:
HD 308 S2 (-OB/-JB)
Black numbered w/ (-JZ) or w/o Green/Yellow (-OZ)
Outer sheath colour:
Grey (based on RAL 7001)

Electrical characteristics
Tensione di esercizio anime 

300/500V section ≤ 2.5 mm²
450/750V section = 4.00 and 6.00 mm²
0.6/1kV section ≥ 10.00 mm²

Tensione di esercizio guaina esterna 
300/500V section ≤ 2.5 mm² 450/750V section = 4.00 and 6.00 mm² 0.6/1kV section ≥ 10.00 mm²
Tensione di prova 

2000V section ≤ 2.5mm²
2500V section = 4.00 and 6.00 mm²
4000V section ≥ 10.00 mm²

Certifications
Standard 

IEC 60228
IEC 60332-3-24 Cat.C

Reaction to Fire Class 
EN 50575:2016 Cca - s1a, d0, a1
Temperature
Temperatura minima di esercizio 
  • Fixed laying: -40°C
  • ​Occasional mobile laying w/o stress: -5°C
Temperatura massima di esercizio 
  • Fixed laying: +70°C
  • Occasional mobile laying w/o stress: +70°C
Temperatura massima cortocircuito 
+160°C
On request 
  • Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature -10°C
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
Applications 

Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Multi-core LSZH cable for power transport, control, signalling, command and measurement systems with very low smokes and toxic gases emissions. It is particularly suitable in sites exposed to fire hazards and where there is high density of people, such as schools, offices, theaters, hospitals, etc. Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
If stored outdoors, the cable must be protected from UV rays.
300/500V and 450/750V (section ≤ 6.00 mm²): Underground laying is not permitted even if protected.
0.6/1kV (section ≥ 10.00 mm²): Direct or indirect underground laying is permitted (presence of water condiction AD7). 