FTG18OH2M16
Fire resistant and LSZH
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI FTG18OH2M16 <formation> 0,6/1kV CEI 20-45 P.Q.A. PH/F120 <lot> <year> B2CA-S1,D1,A1
Manufacturing characteristics
Core
Flexible bare copper, class 5
Insulation
LSZH cross-linked elastrometric compound, G18 type
Stranding
Cores twisted/stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
Overall bare copper braid
Outer sheath
LSZH thermoplastic compound, M16 type
Colours
Cores identification:
CEI UNEL 00722 (HD 308 S2)
Outer sheath colour:
Blue (basato su RAL 5015)
Electrical characteristics
Tensione di esercizio anime
600/1000V
Tensione di esercizio guaina esterna
600/1000V
Tensione di prova
4000V
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C CEI 20-45 P.Q.A.
UNI 9795
- Per Øest. ≤ 20mm: CEI EN 50200 EN 50200 (Duration test 120 min. PH120)
- Per Øest. >20mm: CEI EN IEC 60331-1 (Duration test 120 min. F120)
Reaction to Fire Class
EN 50575:2016 B2ca - s1a, d1, a1
Temperature
Temperatura minima di esercizio
-40°C
Temperatura massima di esercizio
+90°C
Temperatura massima cortocircuito
+250°C
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d14
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
The cable stored outside must be protected from UV rays
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
LSZH multi-core cable with screen for power, insulated with elastometric compound non-flame-propagating and halogen free, with flexible cores protected by fireproof barrier.
Suitable for emergency systems in locations with danger of explosion and fire (exits and security lightings, alarm signals, smokes and gases detectors, esclators, fire pumps, fire curtains, etc.).
If stored outdoors, the cable must be protected from UV rays. Direct or indirect underground laying is permitted.