FTE29OHM16AM16 PH120
Aluminium conductor - Fire resistant and LSZH
Marcatura
<meters> CE SPECIALCAVI BALDASSARI FTE29OHM16AM16 PH120 <formation> EN 50200 CEI 20-105 P.Q.A. GUAINA 0.6/1kV <lot> <year> CCA-S1B,D1,A1
Manufacturing characteristics
Core
Flexible bare copper, class 5
Insulation
LSZH cross-linked compound, E29 type
Stranding
Cores twisted/stranded in concentric layers
Wrapping and protection
Screen
Overall aluminium/polyester tape with flexible bare copper drain-wire
Inner sheath
LSZH thermoplastic compound, M16 type
Armour
Overall galvanized steel braid
Outer sheath
LSZH thermoplastic compound, M16 type, oil and hydrocarbons resistant
Colours
Cores colour:
2 cores = Red + Black
Colore outer sheath:
Red (based on RAL 3000)
Electrical characteristics
Tensione di esercizio anime
100/100V
Tensione di esercizio guaina esterna
600/1000V
Tensione di prova
2000V
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI 20-105:2024 P.Q.A.
CEI 20-36/4-0 EN 50200 (Duration test 120 min. PH120)
UNI 9795:2021
Reaction to Fire Class
EN 50575:2016 Cca - s1b,d1,a1
Temperature
Temperatura minima di esercizio
-40°C
Temperatura massima di esercizio
+90°C
Temperatura massima cortocircuito
+250°C
On request
- Customized cores identification/outer sheath colours
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d14
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In duct or cable tray
In buried trough
Buried with protection
In buried duct
Directly buried
The cable stored outside must be protected from UV rays
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
LSZH shielded/armoured cable for signalling and command, fire-resistant (PH120) according to CEI 20-105:2024 P.Q.A.,
P.Q.A. and UNI 9795:2021 with outer sheath with reinforced thickness. It can be used for connecting fixed automatic detection and manual fire alarm signalling systems, whether or not connected to fire extinguishing systems (both active and passive types), planned to be installed in buildings, regardless of their intended use. Suitable for links between fire-fighting systems and actuators (e.g. electric locks, smoke and heat natural evacuators, electromagnets for releasing fire doors, etc.) with 12V and 24V AC operating voltage.
This cable can also be installed in coexistence with 450/750V or 0.6/1kV power cables that supply 230/400V nominal voltage loads.
If stored/placed outdoors, the cable must be protected from UV rays.
Outdoors laying is permitted with UV protection; direct or indirect underground laying is permitted.