FG18OH2M16 B2ca
Power, control and signalling - Low smoke zero halogen
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI FG18OH2M16 <formation> 0,6/1kV CEI EN 60332-3-24 <lot> <year> B2CA-S1A,D0,A1
Manufacturing characteristics
Core
Flexible bare copper, class 5
Insulation
HERP rubber compound, G18 type
Stranding
Cores twisted/stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
Overall bare copper braid
Outer sheath
LSZH thermoplastic compound, M16 type
Colours
Cored identification:
CEI UNEL 00722 – 00725 (HD 308 S2 – EN50334)
Outer sheath ncolour:
Black (based on RAL 9005)
Electrical characteristics
Tensione di esercizio anime
0.6/1kV
Tensione di esercizio guaina esterna
0.6/1kV
Tensione di prova
4000V
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI 20-38 P.Q.A.
Reaction to Fire Class
EN 50575:2016 B2ca - s1a, d0, a1
Temperature
Temperatura minima di esercizio
-40°C
Temperatura massima di esercizio
+90°C
Temperatura massima cortocircuito
+250°C
On request
• Galvanized steel braid armour
• Customized cores identification/outer sheath colours
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d10
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In open air
In duct or cable tray
In buried trough
Buried with protection
In buried duct
Directly buried
The cable stored outside must be protected from UV rays
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
LSZH multi-core cable for power and signalling with very low smokes and toxic gases emissions.
It’s particularly suitable in sites exposed to fire hazards such as terminals, railway and maritime stations, subways, road tunnels with lenght more than 500 m and railway tunnels more than 1000 m.
It’s suitable for laying in wet locations and it can be installed on walls and metallic frames, in ducts, cable trays and similar systems.
The shield protects from electromagnetic interferences.
If stored/layed outdoors, the cable must be protected from UV rays.
Direct or indirect underground laying is permitted.