ULX FRXOHR16 Cca
Data transmission and instrumentation
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI ULX FRXOHR <formation> 450/750V IEC 60332-3-24 <lot> <year> DCA-S3,D0,A3
Manufacturing characteristics
Core
Flexible tinned copper
Insulation
PVC compound, R2 type
Stranding
Cores twisted in pairs
Pairs stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
Overall aluminium/polyester tape with flexible tinned copper drain-wire
Outer sheath
PVC compound, R16 type
Colours
Colori anime:
DIN 47100
Colore guaina esterna:
Grigio (basato su RAL 7035)
Electrical characteristics
Tensione di esercizio anime
300/300V
Tensione di esercizio guaina esterna
450/750V
Tensione di prova
1500V
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI UNEL 36762
Reaction to Fire Class
EN 50575:2016 Cca - s2, d0, a3
Temperature
Temperatura minima di esercizio
-15°C
Temperatura massima di esercizio
+70°C
Temperatura massima cortocircuito
+160°C
On request
• Armatura a treccia di acciaio zincato con guaina esterna con tensione isolamento 450/750V
• Guaina esterna con tensione 0.6/1kV per posa in esterno o in cavidotto interrato
• Colori anime/guaina personalizzati
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d10
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In open air
In duct or cable tray
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Overall shielded multipair cable suitable for electronic, data transmission between central and peripheral units through ports (RS232) and for interconnections between devices where a high quality of the transmitted signals is required.
This cable can always be installed in coexistence with 450/750V power cables. Furthermore, if it’s used to supply power
to category 0 systems (nominal voltage less than or equal to 50V AC, or 120V non-inverted DC), it can also be installed in coexistence with 0.6/1kV power cables that supply 230/400V nominal voltage loads.
Underground laying is not permitted, even if protected.