HSLH-OB/-JB/-OZ/-JZ Cca
Power, control and signalling - Low smoke zero halogen
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI HSLH <formation> IEC 60332-3-24 <lot> <year> CCA-S1A,D0,A1
Manufacturing characteristics
Core
Flexible bare copper conductor, class 5
Insulation
LSZH thermoplastic compound, TI6 type
Stranding
Cores twisted/stranded in concentric layers
Outer sheath
LSZH thermoplastic compound, TM7 type
Colours
Cores identifcation:
HD 308 S2 (-OB/-JB)
Black numbered w/ (-JZ) or w/o Green/Yellow (-OZ)
Outer sheath colour:
Grey (based on RAL 7001)
Electrical characteristics
Tensione di esercizio anime
• 300/500V section ≤ 2.5 mm2 • 450/750V section = 4.00 and 6.00 mm2 • 0.6/1kV section ≥ 10.00 mm2
Tensione di esercizio guaina esterna
• 300/500V section ≤ 2.5 mm2
• 450/750V section = 4.00 and 6.00 mm2
• 0.6/1kV section ≥ 10.00 mm2
Tensione di prova
• 2000V section ≤ 2.5mm2 • 2500V section = 4.00 and 6.00 mm2 • 4000V section ≥ 10.00 mm2
Certifications
Standard
IEC 60228
IEC 60332-3-24 Cat.C
Reaction to Fire Class
EN 50575:2016 Cca - s1a, d0, a1
Temperature
Temperatura minima di esercizio
• Fixed laying -40°C • Occasional mobile laying w/o stress -5°C
Temperatura massima di esercizio
• Fixed laying +70°C • Occasional mobile laying w/o stress +70°C
Temperatura massima cortocircuito
+160°C
On request
• Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Multi-core LSZH cable for power transport and for control, signaling, command and measurement systems with very low smoke and toxic gas emission. It is particularly suitable in sites exposed to fire hazards and where there is a high density of people, such as schools, offices, theaters, hospitals, etc. Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
If stored outdoors, the cable must be protected from UV rays.
300/500V and 450/750V: Underground laying is not permitted even if protected.
0.6/1kV: Direct or indirect underground laying is permitted.