1Z2AZ2-K
Solar energy
Marcatura
CE 0987 SPECIALCAVI BALDASSARI 1Z2AZ2-K <formation> <lot> <year> ECA
Manufacturing characteristics
Core
Flexible bare copper, class 5
Insulation
Special LSZH cross-linked elastrometric compound
Wrapping and protection
Polyester tape
Armour
Galvanized steel braid
Outer sheath
Special LSZh cross-linked elastrometric compound, UV resistant
Colours
Cores identification:
White
Outer sheath colour:
Black or Red (based on RAL 9005 o 3000)
Electrical characteristics
Tensione di esercizio anime
Nominal operating voltage: 1.5kV C.C. (also to earth)
Maximum operating voltage: 1.8kV C.C. (also to earth)
Tensione di esercizio guaina esterna
Nominal operating voltage: 1.5kV C.C. (also to earth)
Maximum operating voltage: 1.8kV C.C. (also to earth)
Tensione di prova
15kV C.C.
Certifications
Standard
EN 50618 p.q.a.
EN 60228 EN 50395
EN 50618 p.q.a.
EN 50618 p.q.a. EN 50395 EN 62230
EN 50618 p.q.a. EN 50396 EN 60228
EN 60811-401 EN 50618 p.q.a.
EN 60811-504 EN 60811-505 EN 60811-506 EN 50618 p.q.a. EN 60811-403 EN 50396 EN 50618 p.q.a.
EN 50618 p.q.a. EN 50289-4-17 metodo A
EN 50618 p.q.a.
EN 60068-2-78
EN 60811-503
EN 60332-1-2
EN 61034-2 (LT≥60%)
EN 50525-1
EN 50618 p.q.a. EN 60216-1 EN 60216-2
Reaction to Fire Class
EN 50575:2016 Eca
Temperature
Temperatura minima di esercizio
-40°C
Temperatura massima di esercizio
+90°C
Temperatura massima cortocircuito
+250°C
On request
- Galvanized steel wires armour
- Aluminium conductor
Laying conditions
Temperatura minima di posa -25°C
Laying operation bending radius d14
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In open air
In duct or cable tray
In buried trough
Buried with protection
In buried duct
Directly buried
Applications
Cable for fixed laying conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Single-core, halogen free and armoured cable suitable for interconnecting various components in solar and photovoltaic systems, only to be used in DC.
1Z2AZ2-K cable has an excellent resistance to UV rays and weather conditions; furthermore it’s highly recommended for underground laying, also direct, because the armour offers excellent protection against rodents attack.
The cable is estimated to operate about 25 years (EN 50618). The period expected for its use at 120°C maximum core temperature and at 90°C maximum ambient temperature is limited to 20.000 hours. Suitable for fixed laying outdoors and inside buildings, without protection or inside visible or embedded pipes. Suitable for applications not covered by CPR Regulations and for installations in a closed environment, excluding cases with specific initiation/propagation fire hazards where is recommended the use of cables with higher fire response performance (at least Cca-s3,d1,a3).
Direct or indirect underground and outside laying is permitted. Presence of water: condition AD8 (adapted to EN 50525-2-21).