FTE29OHM16 PH120
Fire resistant and LSZH
Marcatura
<meters> CE SPECIALCAVI BALDASSARI FTE29OHM16 PH120 100/100V <formation> EN 50200 CEI 20-105 C-4 (U0=400V) <lot> <year> CCA-S1B,D1,A1
Manufacturing characteristics
Core
Flexible bare copper, class 5
Insulation
LSZH cross-linked compound, E29 type
Stranding
Cores twisted/stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
Overall aluminium/polyester tape with flexible bare copper drain-wire
Outer sheath
LSZH thermoplastic compound, M16 type
Colours
Cores identification:
2 cores = Red + Black
4 cores = Red + Black + White + Blue
Outer sheath colour:
Red (based on RAL 3000)
Electrical characteristics
Tensione di esercizio anime
100/100V
Tensione di esercizio guaina esterna
100/100V C-4 (U0=400V)
Tensione di prova
2000V
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Cat.C IEC 60332-3-24 Cat.C
CEI 20-105:2024 CEI UNEL 35338
CEI 20-36/4-0 EN 50200 (Durata test 120 min. PH120)
CEI UNEL 36762
UNI 9795:2021
Reaction to Fire Class
EN 50575:2016 Cca - s1b,d1,a1
Temperature
Temperatura minima di esercizio
-40°C
Temperatura massima di esercizio
+90°C
Temperatura massima cortocircuito
+250°C
On request
- Customized cores identification/outer sheath colours
- Reinforced outer sheath for underground laying in duct
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius d14
Max tensile stress: 50N/mm^2 of the copper cross-section
Fixed Laying
In duct or cable tray
The cable stored outside must be protected from UV rays
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
LSZH shielded cable for signalling and command, fire-resistant (PH120) according to CEI 20-105:2024, CEI UNEL 35338 and UNI 9795:2021.
It can be used for connecting fixed automatic detection and manual fire alarm signalling systems, whether or not connected to fire extinguishing systems (both active and passive types), planned to be installed in buildings, regardless of their intended use.
Suitable for links between fire-fighting systems and actuators (e.g. electric locks, smoke and heat natural evacuators, electromagnets for releasing fire doors, etc.) with 12V and 24V AC operating voltage.
This cable, if it’s used to supply power to category 0 systems (nominal voltage less than or equal to 50V AC, or 120V noninverted DC), it can also be installed in coexistence with 450/750V or 0.6/1kV power cables that supply 230/400V nominal voltage loads.
If stored outdoors, the cable must be protected from UV rays. Underground laying is not permitted, even if protected.