2XSLCYK-J MOTOR 3+3PE Dca
Power, control and signalling
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI 2XSLCYK-J <formation> <lot> <year> DCA-S3,D2,A3
Manufacturing characteristics
Core
Flexible bare copper conductor, class 5
Insulation
XLPE compound
Stranding
Cores stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
1st screen:
Overall aluminium/polyester tape
2nd screen:
Overall tinned copper braid
Outer sheath
Flame retardant PVC compound
Colours
Cores identification:
Brown + Black + Grey + 3 x Green/Yellow
Outer sheath colour:
Black (based on RAL 9005)
Electrical characteristics
Tensione di esercizio anime
0.6kV
Tensione di esercizio guaina esterna
1.8kV D.C. and 1.2kV A.C.
Tensione di prova
4000V
Certifications
Standard
IEC 60228
Reaction to Fire Class
EN 50575:2016 Dca - s3, d2, a3
Temperature
Temperatura minima di esercizio
- Fixed laying: -25°C
- Occasional mobile laying w/o stress: -5°C
Temperatura massima di esercizio
- Fixed laying: +90°C
- Occasional mobile laying w/o stress: +90°C
Temperatura massima cortocircuito
+250°C
On request
- Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature -10°C
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Screened cable characterized by its special construction, used to power motors with frequency converters when full electromagnetic compatibility (EMC) is required.
The symmetrical construction of the cable (3 + 3PE) ensures the symmetry of the supply voltages on the motor terminals.
Suitable for both static and dynamic connections (occasional movement) in industrial plants, process lines and machines operating in dry and humid environments.
Direct or indirect underground laying is permitted. Underground outdoors laying is not permitted even if protected (presence of water condiction AD7).