YSLY-OB/-JB/-OZ/-JZ Cca
Power, control and signalling
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI YSLY <formation> IEC 60332-3-24 <lot> <year> CCA-S2,D0,A3
Manufacturing characteristics
Core
Flexible bare copper conductor, class 5
Insulation
Flame retardant PVC compound
Stranding
Cores twisted/stranded in concentric layers
Outer sheath
Flame retardant PVC compound
Colours
Cores identifcation:
HD 308 S2 (-OB/-JB)
Black numbered w/ (-JZ) or w/o Green/Yellow (-OZ)
Outer sheath colour:
Grey (based on RAL 7001)
Electrical characteristics
Tensione di esercizio anime
- 300/500V section ≤ 2.5 mm²
- 450/750V section = 4.00 and 6.00 mm²
- 0.6/1kV section ≥ 10.00 mm²
Tensione di esercizio guaina esterna
300/500V section ≤ 2.5 mm²
450/750V section = 4.00 and 6.00 mm²
0.6/1kV section ≥ 10.00 mm²
Tensione di prova
- 2000V section ≤ 2.5mm²
- 2500V section = 4.00 and 6.00 mm²
- 4000V section ≥ 10.00 mm²
Certifications
Standard
IEC 60228
IEC 60332-3-24 Cat.C
Reaction to Fire Class
EN 50575:2016 Cca - s2, d0, a3
Temperature
Temperatura minima di esercizio
- Fixed laying: -25°C
- Occasional mobile laying w/o stress: -5°C
Temperatura massima di esercizio
- Fixed laying: +70°C
- Occasional mobile laying w/o stress: +70°C
Temperatura massima cortocircuito
+160°C
On request
- Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature -10°C
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
Buried with protection (0.6/1kV)
In buried duct (0.6/1kV)
Directly buried (0.6/1kV)
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
Multi-core cable for power transport and for control, signaling, command and measurement systems with scaled-down outer dimensions and excellent flexibility.
Used in industry for machine cabling, transport systems, production lines and in the connection of air conditioning and heating systems, industrial equipment and power stations. Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
300/500V and 450/750V: Underground laying is not permitted even if protected.
0.6/1kV: Direct or indirect underground laying is permitted.