LiHCH-TP-DIN B2ca
Low smoke zero halogen - Data transmission and instrumentation
Marcatura
<meters> CE 0987 SPECIALCAVI BALDASSARI LIHCH-TP <formation> IEC 60332-3-24 <lot> <year> B2CA-S1A,D0,A1
Manufacturing characteristics
Core
Flexible bare copper conductor, class 5
Insulation
LSZH thermoplastic compound, TI6 type
Stranding
Cores twisted in pairs
Pairs stranded in concentric layers
Wrapping and protection
Overall polyester tape
Screen
Overall tinned copper braid
Outer sheath
LSZH thermoplastic compound, TM7 type
Colours
Cores identification:
DIN 47100
Outer sheath colour:
Grey (based on RAL 7001)
Electrical characteristics
Tensione di esercizio anime
• 300V section ≤0,75 mm²
• 500V section ≥1,00 mm²
Tensione di esercizio guaina esterna
450/750V
Tensione di prova
• 2000V section ≤0,75 mm²
• 2500V section ≥1,00 mm²
Certifications
Standard
CEI 20-29 IEC 60228
CEI 20-11
CEI EN 60332-3-24 Car.C IEC 60332-3-24 Cat.C
CEI UNEL 36762
Reaction to Fire Class
EN 50575:2016 B2ca - s1a, d0, a1
Temperature
Temperatura minima di esercizio
- Fixed laying: -40°C
- Occasional mobile laying w/o stress: -5°C
Temperatura massima di esercizio
- Fixed laying: +70°C
- Occasional mobile laying w/o stress: +70°C
Temperatura massima cortocircuito
+160°C
On request
- Customized cores identification/outer sheath colour
Laying conditions
Minimum installation temperature 0°
Laying operation bending radius: see technical data sheet
Max tensile stress: see tecnica data sheet
Fixed Laying
Posa mobile occasionale aciclica senza stress
In open air (0.6/1kV)
In duct or cable tray
In buried trough (0.6/1kV)
The cable stored outside must be protected from UV rays
Applications
Cable conforms to the requirements in the Construction Products Regulations (CPR EU 305/11), aimed at limiting the production and diffusion of fire and smoke.
LSZH multi-pair cables with overall screening for data transmission in electronics and computers, for signaling, measurement, command and control systems, and more generally, where there is a need for efficient protection from external electromagnetic disturbance and compact size.
It is particularly suitable in sites exposed to fire hazards and where there is a high density of people, such as schools, offices, theaters, hospitals, etc.
Suitable for installation in dry or damp indoor environments, in static or limited dynamic installation (not permanently in motion) where there is no mechanical stress.
If stored outdoors, the cable must be protected from UV rays.
Underground laying is not permitted even if protected.